Essex
Electro Motor Generator Set
Serial
Number 204
MODEL
NO. A700A
|
 |
FUNCTIONAL
DESCRIPTION:
Model A700A is intended for use in supplying
high quality, closely regulated, 400-cycle power for hangers,
maintenance shops, instructional facilities and other installations
requiring precise power. The Motor Generator Set is a
self-contained, forced air-cooled skid mounted unit. The unit basically
consists of a motor generator,
instruments, controls, and terminal board; all mounted within a sheet
metal housing. Rotating
brushless exciters are supplied for both the motor and the generator.
A solid state voltage regulator is supplied for controlling the
output of the generator. Voltage
and current protective devices are furnished to protect the input and
output circuits.
OVERALL
DIMENSIONS AND WEIGHT:
Height:
41 Inches Length: 88-3/4 Inches Depth: 36-1/2Inches Weight (Dry): 3,920
Lbs.
TECHNICAL
DESCRIPTION:
Output
Rating ................................... 62.5 KVA, 0.8 power factor,
120/208 Volt, 3-phase, 4 wire, 400 Hertz,
175
Ampere
62.5
KVA, 0.8 power factor, 120 Volt, 3 phase, 3 wire, 400 Hertz,
Delta
Connected, 303 Ampere
62.5
KVA, 0.8 power factor, 120 Volt, 1 phase, 2 wire, 400 Hertz,,
Delta
Connected, 520 Ampere
Input
Rating ...................................... 220/440 Volt, 3 phase, 60
Hertz
154
Amperes at 220 Volts
77
Amperes at 440 Volts
Starting
Current ................................ 500 Amperes at 220 Volts
250
Amperes at 440 Volts
Voltage-
Regulation .......................... 1% no load to full load
Voltage
Transient ............................. 20% maximum upon full load
application or rejection
Voltage
Modulation .......................... 1/4%
Voltage
Unbalance ........................... 1% maximum for balance 3 phase
loads
Voltage
Response Time .................... 0.2 second to within 2% of rated
voltage upon application or rejection
of
full load
Harmonic
Content............................. 2% Total
Frequency
Response Time................ 3 seconds to within ± 1/2 cycle upon
application or rejection of full load
Circuit
Protection .............................. A protective module which
protects the unit from input overvoltage, output overvoltage, and output
overcurrent. Overload relays for input
overload
protection
Input
Voltmeter................................. 0-500 Volt, 2% Accuracy, 60
Hertz
Output
Voltmeter .............................. 0-150 Volt, 2% Accuracy, 400
Hertz
Output
Ammeter System .................. 0-250 Amperes, 3% Accuracy, 400 Hertz
Output
Frequency Meter ................... 390-410 Hertz, Accuracy ± 1.0 Hertz
at 400 Hertz and 120 Volts
Running
Time Meter ........................ 0-9999.99 Hours
Input
and Output Terminals .............. Stud type connections for 3/8 lugs
Operating
Temperature Range.......... -46°C to +55°C
Optional
Features .............................. Trailer Mounted; Cable Assembly
- Input Cable; Output AC Cable;
Output
DC Cable; DC Power Supply - 28 VDC - 500 Amps
|